<strong>GE</strong> Oil <strong>and</strong> Gas<br />

<strong>SVI</strong> <strong>II</strong> <strong>AP</strong> Instruction Manual<br />

NOTE<br />

For HART 6 units, the <strong>Maintenance</strong> Required response under<br />

Additional Status does not indicate any maintenance need.<br />

Proceed with the following steps:<br />

1. Press NEXT.<br />

2. Field device has more status available.<br />

3. Press NEXT.<br />

4. Ignore next 50 occurrences of status?<br />

5. Press YES.<br />

6. Change to MANual mode.<br />

7. Scroll to line 6 EXAMINE, press ->.<br />

8. Scroll down to 5 read status.<br />

9. Read message.<br />

10. Press OK.<br />

11. Repeat OK to read all messages until the display returns to read status.<br />

12. Scroll down to 6 clear status, press ->.<br />

13. If clear fault codes not completed appears, press OK <strong>and</strong> read the message (Position<br />

Error, for example) or go to the troubleshooting guide.<br />

14. Correct the problem (Is the air supply on?), <strong>and</strong> then go to clear status until Clear<br />

Fault codes Completed appears.<br />

15. Press OK.<br />