Load Specifications<br />
Recommended Load Specifications<br />
Table 17 lists the operational specifications of the switches. These switches receive 24<br />
VDC on/off signals.<br />
Table 17<br />
Item<br />
Rated Input Voltage (from relay)<br />
Switch Operational Specifications<br />
24 VDC (sink/source)<br />
Specification<br />
Input ON Voltage 18 to 26.4<br />
Input ON Voltage<br />
5.0 V or less<br />
Checking Switch Operation<br />
ValVue Comm<strong>and</strong>s<br />
This procedure is an example, using the settings in Figure 73, to verify switch operation:<br />
1. Click the Configure tab, click <strong>and</strong> Figure 73 appears.<br />
Figure 73<br />
I/O Configure<br />
2. Switch from Normally Opened to Normally Closed or vice versa, click OK <strong>and</strong> Apply.<br />
3. Click the Monitor tab.<br />
4. Select Comm<strong>and</strong> 142 Read Switches from the pulldown list <strong>and</strong> click OK. The<br />
information field below populates with the configured switch states.<br />
5. Ensure that the switch just reconfigured has changed state.<br />