Cabling <strong>and</strong> Interconnection<br />

Wiring an <strong>SVI</strong> <strong>II</strong> <strong>AP</strong><br />

Cabling <strong>and</strong> Interconnection Requirements<br />

Interconnections are made using shielded twisted pair cables. The shield is connected<br />

to ground at one point only. The signal loop is grounded at only one point in accordance<br />

with plant electrical st<strong>and</strong>ards. It is customary to ground the signal at the controller or<br />

intrinsic safety barrier. The <strong>SVI</strong> <strong>II</strong> <strong>AP</strong> is supplied with two 1/2" NPT conduit entries. M20<br />

adapters are available. Internal <strong>and</strong> external ground terminals are provided for case<br />

grounding requirements.<br />

WARNING<br />

NOTE<br />

Install the <strong>SVI</strong> <strong>II</strong> <strong>AP</strong> in accordance with local <strong>and</strong> national<br />

code in both general <strong>and</strong> hazardous area locations.<br />

Substitution of components can impair suitability for use in<br />

hazardous locations.<br />

The internal electronic components are isolated for ground.<br />

Grounding the case is unnecessary for functional purposes.<br />

Grounding the case may be necessary to conform to local<br />

codes.<br />

Capacitance vs. Length of Cable for HART<br />

The HART Communications Foundations specifies cable capacitance requirements to<br />

preserve signal strength. Refer to the st<strong>and</strong>ards for detailed calculation methods.<br />

CAUTION<br />

Do not connect a HART modem <strong>and</strong> a PC to a control circuit<br />

unless the controller is HART compatible or has a HART<br />

filter. Loss of control or a process upset can occur if the<br />

controller output circuit is not compatible with HART signals.<br />

HART Filter Required for Certain Control System Output Circuits<br />

The <strong>SVI</strong> <strong>II</strong> <strong>AP</strong> is intended for use with all control systems. However, output circuits of<br />

several major DCS systems are incompatible with the tones used for HART signals.<br />

You must verify that the DCS or controller works reliably with the HART protocol. When<br />

the DCS is incompatible an external HART filter must be installed between the field<br />

wiring <strong>and</strong> the output card. MTL manufactures the HART filter HCU16AO. It is a 16<br />

channel DIN rail mounted device composed of passive circuitry that introduces<br />

negligible voltage drop. For additional information, contact MTL.<br />

NOTE<br />

A control circuit must be HART compatible or have a<br />

HART filter installed. Contact the manufacturer of the<br />

controller or DCS. See “HART Filter Requirements” on<br />

page 125. of this manual for more information.<br />

113