Configuring <strong>and</strong> Calibrating with<br />

Configuration <strong>and</strong> Calibration<br />

Configuring <strong>and</strong> Calibrating with ValVue<br />

ValVue Lite is the most complete <strong>and</strong> easiest to use configuration tool. ValVue Lite is<br />

provided with each <strong>SVI</strong> <strong>II</strong> <strong>AP</strong>. ValVue or ValVue Lite provides a personal computer<br />

interface for configuring <strong>and</strong> calibrating <strong>SVI</strong> <strong>II</strong> <strong>AP</strong>. Use of these tools is recommended.<br />

See the ValVue Instruction Manual on the CD-ROM included with the <strong>SVI</strong> <strong>II</strong> <strong>AP</strong>.<br />

In this section, we recommend a few ValVue Lite steps to checkout <strong>and</strong> configure a<br />

pre-installed <strong>SVI</strong> <strong>II</strong> <strong>AP</strong> on a control valve.<br />

Read <strong>and</strong> Set Configuration Parameters<br />

Change to MANUAL mode<br />

Run Find Stops<br />

Run AutoTUNE<br />

View Calibration Parameters<br />

View Diagnostics<br />

Read <strong>and</strong> Clear Status<br />

Return to NORMAL mode<br />

NOTE<br />

Setting the input current span is unnecessary except for<br />

applications such as split range. Calibration of the input<br />

current sensor requires the use of high accuracy current<br />

st<strong>and</strong>ards. The factory settings should only be changed if a<br />

calibration laboratory detects errors.<br />

Never connect ValVue to an <strong>SVI</strong> <strong>II</strong> <strong>AP</strong> that is in<br />

Configuration or Calibration using pushbuttons.<br />

<strong>Installation</strong> of Cover<br />

The cover of the <strong>SVI</strong> <strong>II</strong> <strong>AP</strong> is a critical component for safety in Hazardous Areas. To<br />

ensure safe operation the flat surfaces of the cover <strong>and</strong> the housing must be clean <strong>and</strong><br />

absolutely free of particles or dents. The O-ring must be securely located in its groove.<br />

Install the cover <strong>and</strong> tighten all four screws. There must be no gap between the housing<br />

<strong>and</strong> cover.<br />