Configuring <strong>and</strong> Calibrating with<br />
Configuration <strong>and</strong> Calibration<br />
Configuring <strong>and</strong> Calibrating with ValVue<br />
ValVue Lite is the most complete <strong>and</strong> easiest to use configuration tool. ValVue Lite is<br />
provided with each <strong>SVI</strong> <strong>II</strong> <strong>AP</strong>. ValVue or ValVue Lite provides a personal computer<br />
interface for configuring <strong>and</strong> calibrating <strong>SVI</strong> <strong>II</strong> <strong>AP</strong>. Use of these tools is recommended.<br />
See the ValVue Instruction Manual on the CD-ROM included with the <strong>SVI</strong> <strong>II</strong> <strong>AP</strong>.<br />
In this section, we recommend a few ValVue Lite steps to checkout <strong>and</strong> configure a<br />
pre-installed <strong>SVI</strong> <strong>II</strong> <strong>AP</strong> on a control valve.<br />
Read <strong>and</strong> Set Configuration Parameters<br />
Change to MANUAL mode<br />
Run Find Stops<br />
Run AutoTUNE<br />
View Calibration Parameters<br />
View Diagnostics<br />
Read <strong>and</strong> Clear Status<br />
Return to NORMAL mode<br />
NOTE<br />
Setting the input current span is unnecessary except for<br />
applications such as split range. Calibration of the input<br />
current sensor requires the use of high accuracy current<br />
st<strong>and</strong>ards. The factory settings should only be changed if a<br />
calibration laboratory detects errors.<br />
Never connect ValVue to an <strong>SVI</strong> <strong>II</strong> <strong>AP</strong> that is in<br />
Configuration or Calibration using pushbuttons.<br />
<strong>Installation</strong> of Cover<br />
The cover of the <strong>SVI</strong> <strong>II</strong> <strong>AP</strong> is a critical component for safety in Hazardous Areas. To<br />
ensure safe operation the flat surfaces of the cover <strong>and</strong> the housing must be clean <strong>and</strong><br />
absolutely free of particles or dents. The O-ring must be securely located in its groove.<br />
Install the cover <strong>and</strong> tighten all four screws. There must be no gap between the housing<br />
<strong>and</strong> cover.<br />