Physical <strong>and</strong> Operational<br />
Table 24<br />
High Flow Pneumatics Single Acting High Flow<br />
Air Supply<br />
Action<br />
Supply Pressure<br />
Dry, oil-free, 5 micron filtered air<br />
(See ISA S7.3)<br />
Direct Acting<br />
20 -100 psi max. (1.4 - 6.9 bar)<br />
Regulate 5 - 10 psi (.345 bar - .69 bar) above actuator spring range.<br />
Do not exceed actuator rating.<br />
Air Delivery - Single Acting Relay<br />
Air Capacity<br />
(flow coefficient)<br />
Air Consumption<br />
39.0 scfm (1100 l/m) at 30 psi (2.1 bar) supply<br />
70.6 scfm (2000 l/m) at 60 psi (4.2 bar) supply<br />
102.0 scfm (2900 l/m) at 90 psi (6.2 bar) supply<br />
Loading CV = 2.2<br />
Venting CV = 2.2<br />
0.28 scfm (8.0 sl/m) at 30 psi (2.1 bar) supply<br />
0.35 scfm (10 sl/m) at 45 psi (3.1bar) supply<br />
Air Supply Failure<br />
Single Acting Relay<br />
On supply failure the actuator output drops. Some overshoot may<br />
occur when air pressure returns after a period without air supply<br />
pressure. Always set control set point to 0%, <strong>and</strong> put the process<br />
control system in manual, for smooth recovery from air supply<br />
failure.<br />
Loss of Input Signal<br />
Output Pressure<br />
Output drops to low pressure.<br />
0-150 psi (10.3 bar) max<br />
151