<strong>GE</strong> Oil <strong>and</strong> Gas<br />

<strong>SVI</strong> <strong>II</strong> <strong>AP</strong> Instruction Manual<br />

Table 11<br />

Error Messages (Continued)<br />

LCD Description Action Cause<br />

EXT DIAG An extended diagnostic procedure failed to complete Warning Pneumatic /<br />

mechanical,<br />

configuration<br />

CMD STOP HART comm<strong>and</strong> aborted Warning Bad data range or<br />

data limitation<br />

BIAS ERR Position algorithm error in output bias Warning Pneumatic/<br />

mechanical<br />

I/P LIMIT I/P current too high or too low Warning Electronic<br />

hardware<br />

TEMP ERR<br />

Internal circuit temperature high (>80° C, 176° F) or<br />

low (