Configure Menu<br />
Because calibration depends on certain configuration options you must perform<br />
Configuration before you perform Calibration when installing the <strong>SVI</strong> <strong>II</strong> <strong>AP</strong> for the first<br />
time.<br />
If a change is made in the Air-to-Open / Air-to-Close configuration option or if you move<br />
the <strong>SVI</strong> <strong>II</strong> <strong>AP</strong> to a different valve or make any change to the valve position linkage, you<br />
must run the find STOPS calibration again.<br />
CONFIG<br />
CONFIGuration Menu<br />
CONFIG<br />
*<br />
Air to<br />
Menu<br />
+ + +<br />
+<br />
+<br />
Char act Pressure Tight Shut-off Language<br />
Menu<br />
Units Menu<br />
Menu<br />
Menu<br />
*<br />
Setup<br />
+<br />
Press * to select option.<br />
Press + or - to accept <strong>and</strong><br />
proceed to next menu item.<br />
Air to....Menu<br />
ATO<br />
*<br />
ATC<br />
Select Air To Open (ATO)<br />
or Air To Close (ATC). Must<br />
match the actuator exactly.<br />
*<br />
Char act<br />
Menu<br />
LINEAR<br />
*<br />
EQ% 30:1<br />
*<br />
EQ% 50:1<br />
*<br />
Pressure Units<br />
Menu<br />
PSI<br />
*<br />
BAR<br />
*<br />
KPA<br />
Turn tight shutoff on or off<br />
to provide maximum actuator<br />
force at 0%<br />
Tight Shutoff<br />
Menu<br />
T.S. OFF<br />
* - +<br />
T.S. ON<br />
*<br />
<br />
*<br />
<br />
*<br />
+/-<br />
Language<br />
Menu<br />
*<br />
ENGLISH<br />
*<br />
FRENCH<br />
Select display language<br />
EQ% CAMFX<br />
*<br />
QUICK50<br />
*<br />
Select display<br />
units for pressure.<br />
Displays tight shutoff<br />
value if turned on.<br />
Press * to change T.S. ON/OFF status.<br />
Press + or - to enter new value.<br />
Press * to accept new value <strong>and</strong> proceed<br />
to next menu item.<br />
CUSTOM<br />
Figure 53<br />
CONFIGure Menu<br />