<strong>GE</strong> Oil <strong>and</strong> Gas<br />

<strong>SVI</strong> <strong>II</strong> <strong>AP</strong> Instruction Manual<br />

Configure Menu<br />

Because calibration depends on certain configuration options you must perform<br />

Configuration before you perform Calibration when installing the <strong>SVI</strong> <strong>II</strong> <strong>AP</strong> for the first<br />

time.<br />

If a change is made in the Air-to-Open / Air-to-Close configuration option or if you move<br />

the <strong>SVI</strong> <strong>II</strong> <strong>AP</strong> to a different valve or make any change to the valve position linkage, you<br />

must run the find STOPS calibration again.<br />

CONFIG<br />

CONFIGuration Menu<br />

CONFIG<br />

*<br />

Air to<br />

Menu<br />

+ + +<br />

+<br />

+<br />

Char act Pressure Tight Shut-off Language<br />

Menu<br />

Units Menu<br />

Menu<br />

Menu<br />

*<br />

Setup<br />

+<br />

Press * to select option.<br />

Press + or - to accept <strong>and</strong><br />

proceed to next menu item.<br />

Air to....Menu<br />

ATO<br />

*<br />

ATC<br />

Select Air To Open (ATO)<br />

or Air To Close (ATC). Must<br />

match the actuator exactly.<br />

*<br />

Char act<br />

Menu<br />

LINEAR<br />

*<br />

EQ% 30:1<br />

*<br />

EQ% 50:1<br />

*<br />

Pressure Units<br />

Menu<br />

PSI<br />

*<br />

BAR<br />

*<br />

KPA<br />

Turn tight shutoff on or off<br />

to provide maximum actuator<br />

force at 0%<br />

Tight Shutoff<br />

Menu<br />

T.S. OFF<br />

* - +<br />

T.S. ON<br />

*<br />

<br />

*<br />

<br />

*<br />

+/-<br />

Language<br />

Menu<br />

*<br />

ENGLISH<br />

*<br />

FRENCH<br />

Select display language<br />

EQ% CAMFX<br />

*<br />

QUICK50<br />

*<br />

Select display<br />

units for pressure.<br />

Displays tight shutoff<br />

value if turned on.<br />

Press * to change T.S. ON/OFF status.<br />

Press + or - to enter new value.<br />

Press * to accept new value <strong>and</strong> proceed<br />

to next menu item.<br />

CUSTOM<br />

Figure 53<br />

CONFIGure Menu<br />

76