<strong>GE</strong> Oil <strong>and</strong> Gas<br />

<strong>SVI</strong> <strong>II</strong> <strong>AP</strong> Instruction Manual<br />

CAUTION<br />

Do not connect a HART modem <strong>and</strong> PC to a control circuit<br />

unless the controller is HART compatible or has a HART filter.<br />

Loss of control or a process upset may occur if the controller<br />

output circuit is not compatible with HART signals.<br />

Install in compliance with Hazardous Area rules in<br />

accordance with local electrical codes <strong>and</strong> plant st<strong>and</strong>ards by<br />

trained specialists.<br />

Do not connect a PC or HART modem to an intrinsically safe<br />

circuit except on the safe area side of the barrier. Do not<br />

operate a PC in a hazardous area without compliance with<br />

local <strong>and</strong> plant regulations.<br />

NOTE<br />

A control circuit must be HART compatible or have a HART<br />

filter installed. Contact the manufacturers of the controller or<br />

DCS. See “HART Filter Requirements” on page 125.<br />

Wiring Guidelines<br />

Comply with current national <strong>and</strong> local regulations for<br />

electrical installation work.<br />

Comply with national <strong>and</strong> local explosive atmosphere<br />

regulations.<br />

Before carrying out any work on the device, power off the<br />

instrument or make sure that the locale conditions for<br />

potentially explosive atmosphere permit the safe opening<br />

of the cover.<br />

This list contains eight guidelines for a successful implementation of DC current signal,<br />

DC power, <strong>and</strong> HART communication to the <strong>SVI</strong> <strong>II</strong> <strong>AP</strong>:<br />

Compliance voltage at the <strong>SVI</strong> <strong>II</strong> <strong>AP</strong> must be 9 V at the maximum current of 20 mA.<br />

Signal to the <strong>SVI</strong> <strong>II</strong> <strong>AP</strong> must be a well-regulated current in the range 3.8 to 22 mA.<br />

Controller output circuit must be unaffected by the HART tones which are in the<br />

frequency range between 1200 <strong>and</strong> 2200 Hz.<br />

Frequency range of the HART tones must have a circuit impedance of more than<br />

220 Ohms, typically 250 Ohms.<br />

HART tones may be imposed by the positioner <strong>and</strong> a communication device<br />

located anywhere on the signaling circuit.<br />

Capacitance of the signaling circuit may not exceed about 0.26 microfarads or with<br />

high series resistance 0.10 microfarads.<br />

Cabling must be shielded to prevent electrical noise that would interfere with the<br />

HART tones, with the shield grounded at only one location.<br />

Signal must be properly grounded in only one place.<br />

106