<strong>GE</strong> Oil <strong>and</strong> Gas<br />

<strong>SVI</strong> <strong>II</strong> <strong>AP</strong> Instruction Manual<br />

To determine how to display <strong>and</strong> select a specific parameter value or configuration option,<br />

refer to the menu structure diagrams shown in Figure 52 on page 75 through Figure 55<br />

on page 82. When using these diagrams as a map you can move through the menus to<br />

the function you needed.<br />

NOTE<br />

If the pushbuttons are pushed after being locked by ValVue<br />

software, the message LOCKED appears. Refer to the<br />

ValVue User’s Guide for instruction about unlocking the<br />

pushbuttons.<br />

Pushbutton Locks <strong>and</strong> Configuration-Lock Jumper<br />

Before performing any of these functions with the local display you must first ensure that<br />

the pushbuttons are placed in the unlocked mode using ValVue Lite. The positioner ships<br />

in the unlocked mode. See ValVue documentation for more details.<br />

The <strong>SVI</strong> <strong>II</strong> <strong>AP</strong> offers several levels of plant security. It may be desirable, after initial setup,<br />

to lock the pushbuttons so that the <strong>SVI</strong> <strong>II</strong> <strong>AP</strong> parameters cannot be inadvertently changed<br />

by the buttons. Several levels of software modifiable pushbutton locks are provided.<br />

Table 9<br />

Pushbutton Lock Security Level<br />

Level<br />

Security Level 3<br />

Security Level 2<br />

Security Level 1<br />

Access<br />

Allow Local Buttons: Buttons on the <strong>SVI</strong> <strong>II</strong> <strong>AP</strong> are fully enabled.<br />

Lock Out Local Calibration <strong>and</strong> Configuration: Use the buttons to perform operations in<br />

normal operating mode <strong>and</strong> manual mode. Do not go to configure or calibrate mode.<br />

Lock Out Local Manual: Examine variables in normal operating mode but do not put the<br />

valve in manual operating mode. Access to calibrate or configure modes is not available.<br />

Security Level 0 Lock Out All Buttons: The buttons are disabled (level 0).<br />

Hardware Configuration Lock<br />

Additional security is achieved using the hardware configuration-lock jumper shown in<br />

Figure 50 on page 66. When set to secure position, shorting the two-pin header,<br />

configuration <strong>and</strong> calibration are not permitted by the local interface or by remote<br />

communications. Pushbuttons, ValVue <strong>and</strong> <strong>GE</strong>'s DPI620 are locked out, except to<br />

examine configuration, calibration, <strong>and</strong> position. This is similar to Security Level 1 shown<br />

in the Pushbutton Lock Security Level table.<br />

The following pages display the menu structure for operating the <strong>SVI</strong> <strong>II</strong> <strong>AP</strong> using local<br />

pushbuttons.<br />

74