To determine how to display <strong>and</strong> select a specific parameter value or configuration option,<br />
refer to the menu structure diagrams shown in Figure 52 on page 75 through Figure 55<br />
on page 82. When using these diagrams as a map you can move through the menus to<br />
the function you needed.<br />
NOTE<br />
If the pushbuttons are pushed after being locked by ValVue<br />
software, the message LOCKED appears. Refer to the<br />
ValVue User’s Guide for instruction about unlocking the<br />
pushbuttons.<br />
Pushbutton Locks <strong>and</strong> Configuration-Lock Jumper<br />
Before performing any of these functions with the local display you must first ensure that<br />
the pushbuttons are placed in the unlocked mode using ValVue Lite. The positioner ships<br />
in the unlocked mode. See ValVue documentation for more details.<br />
The <strong>SVI</strong> <strong>II</strong> <strong>AP</strong> offers several levels of plant security. It may be desirable, after initial setup,<br />
to lock the pushbuttons so that the <strong>SVI</strong> <strong>II</strong> <strong>AP</strong> parameters cannot be inadvertently changed<br />
by the buttons. Several levels of software modifiable pushbutton locks are provided.<br />
Table 9<br />
Pushbutton Lock Security Level<br />
Level<br />
Security Level 3<br />
Security Level 2<br />
Security Level 1<br />
Access<br />
Allow Local Buttons: Buttons on the <strong>SVI</strong> <strong>II</strong> <strong>AP</strong> are fully enabled.<br />
Lock Out Local Calibration <strong>and</strong> Configuration: Use the buttons to perform operations in<br />
normal operating mode <strong>and</strong> manual mode. Do not go to configure or calibrate mode.<br />
Lock Out Local Manual: Examine variables in normal operating mode but do not put the<br />
valve in manual operating mode. Access to calibrate or configure modes is not available.<br />
Security Level 0 Lock Out All Buttons: The buttons are disabled (level 0).<br />
Hardware Configuration Lock<br />
Additional security is achieved using the hardware configuration-lock jumper shown in<br />
Figure 50 on page 66. When set to secure position, shorting the two-pin header,<br />
configuration <strong>and</strong> calibration are not permitted by the local interface or by remote<br />
communications. Pushbuttons, ValVue <strong>and</strong> <strong>GE</strong>'s DPI620 are locked out, except to<br />
examine configuration, calibration, <strong>and</strong> position. This is similar to Security Level 1 shown<br />
in the Pushbutton Lock Security Level table.<br />
The following pages display the menu structure for operating the <strong>SVI</strong> <strong>II</strong> <strong>AP</strong> using local<br />
pushbuttons.<br />
74