Masoneilan SVI II AP Installation and Maintenance ... - GE Energy
Masoneilan SVI II AP Installation and Maintenance ... - GE Energy
Masoneilan SVI II AP Installation and Maintenance ... - GE Energy
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
<strong>GE</strong> Oil <strong>and</strong> Gas<br />
<strong>SVI</strong> <strong>II</strong> <strong>AP</strong> Instruction Manual<br />
Table 25<br />
Pneumatics Double Acting St<strong>and</strong>ard Flow<br />
Air Supply Dry, oil-free, 5 micron filtered air see ISA S7.3<br />
Action<br />
Supply Pressure for<br />
Double Acting<br />
Air Delivery for<br />
Double Acting<br />
Air Consumption for<br />
Double Acting<br />
Air Supply Failure<br />
Loss of Input Signal<br />
Output 1 increases with increasing<br />
Output 2 decreases with increasing<br />
25 - 150 psi max. (1.73 to 10.3 bar)<br />
Do not exceed actuator rating.<br />
7.2 scfm (203 l/m) at 30 psi (2.1 bar) supply<br />
12.8 scfm (362 l/m) at 60 psi (4.2 bar) supply<br />
18.3 scfm (518 l/m) at 90 psi (6.3 bar) supply<br />
23.8 scfm (674 l/m) at 120 psi (8.4 bar) supply<br />
0.4 scfm (11.3 l/m) at 30 psi (2.1 bar) supply<br />
0.85 scfm (22.6 l/m) at 80 psi (5.52 bar) supply<br />
Positioner cannot control the failure position of an actuator without a spring. The actuator<br />
can, under different conditions, fail in place, fail open, or fail close. In cases where the<br />
valve must fail to a required position additional control equipment is required.<br />
Some overshoot can occur when air pressure returns after a period without air supply<br />
pressure. Always set control set point to 0%, <strong>and</strong> put the process control system in<br />
manual, for smooth recovery from air supply failure.<br />
Output 1 drops to low pressure.<br />
Output 2 rises to supply pressure.<br />
152