<strong>GE</strong> Oil <strong>and</strong> Gas<br />

<strong>SVI</strong> <strong>II</strong> <strong>AP</strong> Instruction Manual<br />

Figure 79<br />

Pneumatic Cover Screws: <strong>AP</strong> (Four Shown)<br />

I/P Module Removal<br />

2. Lift the cover off <strong>and</strong> put aside for installation.<br />

To remove I⁄P module:<br />

1. Disconnect the I/P wire from the terminal board.<br />

2. Using a 3 mm hex key, remove the four screws from around the perimeter of the I⁄P<br />

module.<br />

Figure 80<br />

<strong>SVI</strong> <strong>II</strong> <strong>AP</strong> High Flow Pneumatic Module with Single Acting Relay<br />

3. Lift the module off the positioner.<br />

I/P Module <strong>Installation</strong><br />

To install I⁄P module:<br />

1. Place the module in the designated area on the positioner.<br />

2. Using a 3 mm hex key, install the four screws around the perimeter of the I⁄P module.<br />

3. Replace the I/P wire connector on the terminal board.<br />