Connecting the Air Supply<br />

<strong>Installation</strong> <strong>and</strong> Set Up<br />

Connecting the Air Supply<br />

After the tubing is installed, use the following procedure to connect the air supply.<br />

1. Use a supply of clean, dry compressed air to the filter regulator.<br />

2. Turn on the air supply.<br />

3. Adjust the filter regulator.<br />

4. Supply pressure must be 5 psi - 10 psi (.345 bar - .69 bar)<br />

(34.485 - 68.97 kPa) greater than the spring range of the actuator but may not<br />

exceed the rated actuator pressure. Refer to the valve or actuator instruction<br />

manual.<br />

Wiring the <strong>SVI</strong> <strong>II</strong> <strong>AP</strong><br />

The procedure below outlines wiring the <strong>SVI</strong> <strong>II</strong> <strong>AP</strong>.<br />

WARNING<br />

Comply with current national <strong>and</strong> local regulations for<br />

electrical installation work.<br />

Comply with national <strong>and</strong> local explosive atmosphere<br />

regulations.<br />

Before carrying out any work on the device, power off the<br />

instrument or make sure that the local conditions for<br />

potentially explosive atmosphere permit the safe opening<br />

of the cover.<br />

Connecting to the Control Loop<br />

The <strong>SVI</strong> <strong>II</strong> <strong>AP</strong> digital valve positioner MUST BE grounded according to local<br />

regulations. It is important to maintain correct polarity at all times, otherwise the<br />

positioner may not operate properly. Physically connect the <strong>SVI</strong> <strong>II</strong> <strong>AP</strong> to the control loop<br />

using a cable specified by the HART Communication Foundation. A shielded cable is<br />

recommended.<br />

To communicate using HART:<br />

1. Connect one end of the cable to the control loop's 4 - 20 mA output.<br />

2. Remove the threaded wiring covers on the positioner.<br />

3. Connect the other end of the cable to the <strong>SVI</strong> <strong>II</strong> <strong>AP</strong>. There are two threaded<br />

openings on the positioner. Use the opening with the red plastic insert.<br />

4. Maintain polarity + <strong>and</strong> - respectively.<br />

59