Connecting the Air Supply<br />
<strong>Installation</strong> <strong>and</strong> Set Up<br />
Connecting the Air Supply<br />
After the tubing is installed, use the following procedure to connect the air supply.<br />
1. Use a supply of clean, dry compressed air to the filter regulator.<br />
2. Turn on the air supply.<br />
3. Adjust the filter regulator.<br />
4. Supply pressure must be 5 psi - 10 psi (.345 bar - .69 bar)<br />
(34.485 - 68.97 kPa) greater than the spring range of the actuator but may not<br />
exceed the rated actuator pressure. Refer to the valve or actuator instruction<br />
manual.<br />
Wiring the <strong>SVI</strong> <strong>II</strong> <strong>AP</strong><br />
The procedure below outlines wiring the <strong>SVI</strong> <strong>II</strong> <strong>AP</strong>.<br />
WARNING<br />
Comply with current national <strong>and</strong> local regulations for<br />
electrical installation work.<br />
Comply with national <strong>and</strong> local explosive atmosphere<br />
regulations.<br />
Before carrying out any work on the device, power off the<br />
instrument or make sure that the local conditions for<br />
potentially explosive atmosphere permit the safe opening<br />
of the cover.<br />
Connecting to the Control Loop<br />
The <strong>SVI</strong> <strong>II</strong> <strong>AP</strong> digital valve positioner MUST BE grounded according to local<br />
regulations. It is important to maintain correct polarity at all times, otherwise the<br />
positioner may not operate properly. Physically connect the <strong>SVI</strong> <strong>II</strong> <strong>AP</strong> to the control loop<br />
using a cable specified by the HART Communication Foundation. A shielded cable is<br />
recommended.<br />
To communicate using HART:<br />
1. Connect one end of the cable to the control loop's 4 - 20 mA output.<br />
2. Remove the threaded wiring covers on the positioner.<br />
3. Connect the other end of the cable to the <strong>SVI</strong> <strong>II</strong> <strong>AP</strong>. There are two threaded<br />
openings on the positioner. Use the opening with the red plastic insert.<br />
4. Maintain polarity + <strong>and</strong> - respectively.<br />
59