<strong>GE</strong> Oil <strong>and</strong> Gas<br />
<strong>SVI</strong> <strong>II</strong> <strong>AP</strong> Instruction Manual<br />
Powering Up the <strong>SVI</strong> <strong>II</strong> <strong>AP</strong><br />
WARNING<br />
This process can cause the valve to move. Before proceeding<br />
be sure the valve is isolated from the process. Keep h<strong>and</strong>s<br />
clear from moving parts.<br />
NOTE<br />
When an <strong>SVI</strong> <strong>II</strong> <strong>AP</strong> is turned on it is advisable to apply the air<br />
supply before applying the electrical input signal.<br />
CAUTION<br />
Use of a low impedance voltage source damages the <strong>SVI</strong> <strong>II</strong><br />
<strong>AP</strong>. The <strong>SVI</strong> <strong>II</strong> <strong>AP</strong> input must be a current controlled source.<br />
The <strong>SVI</strong> <strong>II</strong> <strong>AP</strong> will not function normally if connected directly to<br />
a voltage source. However, direct connection to a current<br />
source of up to 30 V will not the damage the <strong>SVI</strong> <strong>II</strong> <strong>AP</strong>. A<br />
proper current source explicitly enables adjustment of the<br />
current in mA, not V.<br />
To power up the <strong>SVI</strong> <strong>II</strong> <strong>AP</strong>:<br />
1. Loosen the four (4) cover screws <strong>and</strong> remove the <strong>SVI</strong> <strong>II</strong> <strong>AP</strong> cover.<br />
2. Connect the +⁄- terminals from the <strong>SVI</strong> <strong>II</strong> <strong>AP</strong> to the current source. Connect + to + <strong>and</strong><br />
- to - (Figure 50 on page 66).<br />
3. Reinstall the cover <strong>and</strong> display.<br />
4. Adjust current to 12 mA. On initial power up of a newly installed <strong>SVI</strong> <strong>II</strong> <strong>AP</strong>, the<br />
positioner starts up in NORMAL mode <strong>and</strong> is operational in the default factory<br />
configuration. The positioner cycles through the NORMAL cycle menu <strong>and</strong> the<br />
following values appear:<br />
PRES: (Pressure - unit of measurement <strong>and</strong> value)<br />
SIGNAL<br />
POS (Position)<br />
An exclamation point (!) in the top left corner of the display window indicates that<br />
there is further instrument status available.*<br />
5. Proceed to Calibration <strong>and</strong> Configuration.<br />
* For firmware version 3.2.1, the supply pressure appears on the LCD. Additionally, Stops<br />
results <strong>and</strong> Autotune results, stay displayed until cleared.<br />
NOTE<br />
If the <strong>SVI</strong> <strong>II</strong> <strong>AP</strong> is specified without local pushbuttons <strong>and</strong><br />
display, local operation is not available. Configure <strong>and</strong><br />
calibrate with ValVue or a H<strong>and</strong> Held HART Communicator.<br />
68