<strong>SVI</strong> <strong>II</strong> <strong>AP</strong> Instruction Manual<br />

Verify Wiring <strong>and</strong> Connections<br />

NOTE<br />

For split range installations there are additional constraints on<br />

the split range system: the minimum span must be 5 mA; the<br />

upper range value must be 8 mA to 20 mA; the lower range<br />

values must be 4 mA to 14 mA.<br />

Use the following procedure to ensure that the <strong>SVI</strong> <strong>II</strong> <strong>AP</strong> is properly powered:<br />

1. Connect a DC voltmeter across the input terminals.<br />

2. For an input current between 4 <strong>and</strong> 20 mA, the voltage varies between 11 V <strong>and</strong> 9 V<br />

respectively.<br />

3. Current is read from the local display or with a milliampmeter installed in series with<br />

the <strong>SVI</strong> <strong>II</strong> <strong>AP</strong>.<br />

4. When voltage exceeds 11 V check that the polarity is correct.<br />

5. If voltage is less than 9 V <strong>and</strong> polarity is correct, voltage compliance of current source<br />

is inadequate.<br />

6. Connect a milliampmeter in series with the current signal. Verify that the source can<br />

supply 20 mA to <strong>SVI</strong> <strong>II</strong> <strong>AP</strong> input.<br />

7. If 20 mA is not attainable, see troubleshooting.<br />

NOTE<br />

Improperly or inadequately grounded installations can cause<br />

noise or instability in the control loop. The internal electronic<br />

components are isolated from ground. Grounding the case is<br />

unnecessary for functional purposes but grounding the case<br />

may be necessary to conform to local codes.<br />

Wiring Considerations<br />

For a detailed description of wiring guidelines refer to “Wiring Guidelines” on page 106 of<br />

this manual.<br />