14.11.2013 Views

Masoneilan SVI II AP Installation and Maintenance ... - GE Energy

Masoneilan SVI II AP Installation and Maintenance ... - GE Energy

Masoneilan SVI II AP Installation and Maintenance ... - GE Energy

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

Padj (%)<br />

Position<br />

Compensation<br />

Damping Coefficient<br />

Dead Zone(%)<br />

Quick Opening<br />

Relay, Pneumatic<br />

Safe Area<br />

Sig Hi<br />

Sig Lo<br />

Single Acting<br />

Split Range<br />

STOPS<br />

Valves often have significantly different response when filling<br />

versus exhausting. The proportional gain is adjusted by adding<br />

Padj to P when the valve is exhausting. Padj is normally less<br />

than P.<br />

The response of the valve is different when the valve is nearly<br />

closed Coefficient than when the valve is nearly open. The position<br />

compensation coefficient, which is a number between 0<br />

<strong>and</strong> 9, allow the control algorithm to optimize the valve<br />

response.<br />

The valve response can be made slower for some applications.<br />

A value of 0 gives no damping, <strong>and</strong> a value of 9 gives maximum<br />

damping of valve motion.<br />

When the valve position is within the setpoint +⁄- the dead zone,<br />

no additional position control is performed. This value is normally<br />

0%, however for high friction valves (e.g. valves with<br />

graphite packing) a higher dead zone helps avoid limit cycling<br />

due to the stick⁄slip action of the valve. In these cases the dead<br />

zone chosen might be 0.2% to 1%.<br />

(see Characteristic)<br />

The component that amplifies the pneumatic control signals to<br />

provide a wide range of actuation pressure <strong>and</strong> to supply <strong>and</strong><br />

vent at high flow rates for responsive control.<br />

The area of a plant where there never is an explosion hazard<br />

present, such as the control room or a wire marshalling rack<br />

area.<br />

In the <strong>SVI</strong> <strong>II</strong> <strong>AP</strong> configuration, the input current setting at which<br />

the valve is fully open (ATO) or fully closed (ATC).<br />

In the <strong>SVI</strong> <strong>II</strong> <strong>AP</strong> configuration, the input current setting at which<br />

the valve is fully closed (ATO) or fully open (ATC).<br />

The action of a position with a single pneumatic output for operation<br />

with a spring return actuator. (see double acting).<br />

A control configuration where a single control output is sent to<br />

two or more control valves. Each control valve positioner is calibrated<br />

to respond to a separate portion of the control signal. An<br />

example is a steam valve <strong>and</strong> a cooling water valve arranged to<br />

be both closed at 50% <strong>and</strong> the steam valve to open.<br />

The <strong>SVI</strong> <strong>II</strong> <strong>AP</strong> runs STOPS procedure to adjust the positioner to<br />

actual valve travel. First the output pressure is reduced to zero<br />

<strong>and</strong> the position is recorded. That position corresponds to 0%.<br />

The output pressure is raised to its maximum based on supply<br />

pressure. The position is recorded <strong>and</strong> corresponds to 100%.<br />

177

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!