<strong>GE</strong> Oil <strong>and</strong> Gas<br />

<strong>SVI</strong> <strong>II</strong> <strong>AP</strong> Instruction Manual<br />

Table 19<br />

Operational Specifications*<br />

Accuracy<br />

Hysteresis <strong>and</strong> Deadb<strong>and</strong><br />

Repeatability<br />

Conformity<br />

Start-Up Drift<br />

Long Term Drift<br />

+/- 0.5% (typical +/-0. 10% or less) Full Span<br />

+/- 0.3% Full Span<br />

+/- 0.3% Full Span<br />

+/- 0.5% Full Span<br />

Less than 0.02% in first hour<br />

Less than 0.003% per month<br />

Position Travel Limits Rotary: 18 - 140°<br />

Reciprocating: 0.25” - 2.5“ (6 mm - 64 mm)<br />

Note: Above 2.5” (64 mm) consult factory for mounting<br />

instructions.<br />

Flow Characteristics<br />

Applied in addition to the control valve’s inherent<br />

characteristic.<br />

Position Auto Tune<br />

<strong>SVI</strong> <strong>II</strong> <strong>AP</strong> performs automatic determination of the<br />

optimal valve position control parameters. In<br />

addition to P, I, D, the position algorithm uses<br />

damping, symmetry for exhaust <strong>and</strong> fill time<br />

constants, dead zone <strong>and</strong> magnitude<br />

characterization parameters. Auto Tune is<br />

optimized for 5% step changes with negligible<br />

overshoot. After the Auto Tune process is<br />

completed, you can further adjust the positioner<br />

tuning parameters to more conservative or to more<br />

responsive values.<br />

Full open position adjustment<br />

Start Up Time (from no power)<br />

Minimum current to maintain HART<br />

Linear<br />

Equal Percentage (of 50:1 or 30:1)<br />

Camflex<br />

Quick Opening (inverse of 50:1 equal percentage)<br />

User Configurable<br />

Tight Shut Off (0 -20% of input)<br />

Proportional gain: 0 to 5, displayed as 0 to 5000<br />

Integral time: 0 to 100 seconds - displayed as 0 to 1000 (1/<br />

10s)<br />

Derivative time: 0 to 200 milliseconds<br />

Dead Zone: 0 to +/-5% (0 to 10% deadb<strong>and</strong>)<br />

Padj: +/- 3000 (depends on P)<br />

Beta (non-linear gain factor): -9 to +9<br />

Stroking Time: 0 to 250 seconds<br />

Position compensation coefficient: 1 to 20<br />

Boost: 0 to 20<br />

60 to 100% of actual stop<br />

Less than 200 ms<br />

3.0 mA<br />

HART Comm<strong>and</strong> #3 Mapping PV = Valve Position, 0-100%<br />

SV = Actuator Pressure (P1-P2)<br />

TV = Supply Pressure<br />

QV = P2 for double acting units<br />

HART 6 Comm<strong>and</strong>s<br />

Cmd 9 - Reads device vars w/status.<br />

Cmd 33 - Reads device variables.<br />

* Specifications are subject to change without notice<br />