<strong>GE</strong> Oil <strong>and</strong> Gas<br />
<strong>SVI</strong> <strong>II</strong> <strong>AP</strong> Instruction Manual<br />
Return to Normal Operation<br />
Always return the positioner to NORMAL operating mode to resume control by the input<br />
signal. Use this procedure to return to NORMAL mode from any menu.<br />
1. Press + or - repeatedly until MANUAL or NORMAL appears.<br />
2. Press:<br />
* to return to NORMAL operating mode, if NORMAL appears.<br />
* to return to MANUAL Mode menu, if MANUAL appears.<br />
3. Press + repeatedly until -› NORMAL appears.<br />
4. Press * to return to NORMAL mode <strong>and</strong> normal operation.<br />
NOTE<br />
When entered from NORMAL mode the valve still responds to<br />
changes in set point input signal <strong>and</strong> the values displayed<br />
change in accordance with changes in the input signal. When<br />
entered from MANUAL mode the valve is in locked position.<br />
H<strong>and</strong> Held Communicator<br />
For communication to a HART device, there is a Device Description Language. A Device<br />
Description, DD, is published by registration with the HART Communication Foundation.<br />
When the DD is installed in a host communication device then the host can readily access<br />
all the information in the smart field device. The <strong>SVI</strong> <strong>II</strong> <strong>AP</strong> registered DD will be available<br />
from HART Communication Foundation when it next publishes the HART DD. The <strong>SVI</strong> <strong>II</strong><br />
<strong>AP</strong> DD can be obtained from the website or by contacting your local representative.<br />
CAUTION<br />
Do not connect a HART modem <strong>and</strong> PC to a control circuit<br />
unless the controller is HART compatible or has a HART filter.<br />
Loss of control or a process upset may occur if the controller<br />
output circuit is not compatible with HART signal.<br />
WARNING<br />
Do not Connect a PC or HART modem to an intrinsically safe<br />
circuit except on the safe area side of the barrier. Do not<br />
operate a PC in a hazardous area without compliance to local<br />
<strong>and</strong> plant regulations.<br />