Specifications <strong>and</strong> References<br />
A<br />
Physical <strong>and</strong> Operational Specifications<br />
This section provides the physical <strong>and</strong> operational specifications for the <strong>SVI</strong> <strong>II</strong> <strong>AP</strong>.<br />
Table 18<br />
Environmental Specifications<br />
Operating Temperature Limits -58° F to 185° F (-50° C to 85° C)<br />
Storage Temperature Limits -58° F to 200° F (-50° C to 93° C)<br />
Temperature Effect < 0.005% /° F typical; -40° F to 180° F (< 0.01% /° C typical; -40° C to 82° C)<br />
Supply Pressure Effect<br />
Relative Humidity<br />
Humidity Effect<br />
Insulation Resistance<br />
MTBF<br />
Electromagnetic Compatibility<br />
Electrostatic<br />
0.05% per psi unit (.73% per bar unit)<br />
10 to 90% non-condensing<br />
Less than 0.2% after 2 days at 104° F (40° C), 95% Relative Humidity.<br />
Greater than 10 G Ohms at 50% RH.<br />
49 years based on MIL h<strong>and</strong>book calculation for electronic parts <strong>and</strong> field data on<br />
mechanical parts<br />
Electrostatic discharge — No effect with contact discharge level of 4 kV <strong>and</strong> air<br />
discharge level of 8 kV<br />
(IEC 1000-4-2)<br />
Radio frequency interference — Less than 0.2% at 10 V per meter<br />
(EN 50140)<br />
Fast Transient Burst No effect at 2 kV (Coupling clamp IEC 1000-4-4).<br />
Vibration Influence<br />
Measured at <strong>SVI</strong> <strong>II</strong> <strong>AP</strong> Housing<br />
Magnetic Field Influence<br />
4 mm at 5 - 15 Hz - Negligible<br />
2 G at 15 - 150 Hz Less than 2 % of span<br />
1 G at 150 - 2000 Hz - Less than 2% of span<br />
Negligible at 30 A/m (EN61000-4-8)<br />
CE MARK certified to EN50081-2 <strong>and</strong> EN50082-2<br />
147