Balance Pressure<br />

Actuator Piping<br />

The double-acting relay is designed to deliver pressure on both sides of a piston type<br />

actuator, so that the cylinder can provide the required thrust <strong>and</strong> stiffness. This stiffness is<br />

factory adjusted to 70% of the supply pressure. This means that, without any unbalance<br />

forces from the valve stem, both outputs deliver roughly 70% of air supply pressure.<br />

Although it is not recommended, the stiffness can be adjusted by moving the Adjustable<br />

Seat assembly up or down.<br />

Connect Output 1, labeled ACT 1 to the inlet port of the actuator in accordance with<br />

Figure 45. Output 2 labeled ACT 2 connects to the opposing actuator port.<br />

Figure 45<br />

Double Acting Positioner ATO⁄ATC Settings for Reciprocating Valves<br />

58