Pneumatic Module<br />

Operation <strong>and</strong> <strong>Maintenance</strong><br />

Double Acting Pneumatic Relay<br />

The double acting pneumatic relay amplifies the pressure from the I/P <strong>and</strong> provides a<br />

pair of high flow output signals for operating a double acting cylinder actuator. The<br />

double acting relay operates on any supply pressure that is at least 5 psi (.345 bar, 34.5<br />

kPa) above the required actuator pressure, up to 150 psi (10.35 bar, 1035 kPa). The<br />

two output pressures may be balanced by means of an adjustable seat assembly. The<br />

average of the two pressures is adjusted to equal 70% of the supply pressure. The<br />

double acting relay is rated for supply pressure to 150 psi (10.35 bar, 1035 kPa).<br />

I/P Current to Pneumatic Converter<br />

Output 2 Gauge<br />

Double Acting<br />

Relay<br />

Vent<br />

Output 1 Gauge<br />

Supply Gauge<br />

Supply Inlet<br />

Output 1 "Act 1"<br />

Output 2 " Act 2"<br />

Figure 76 Double Acting Pneumatic Relay<br />

Double Acting Supply Pressure Balance<br />

After installation on the actuator, set supply pressure in accordance with actuator<br />

specifications. Do not exceed the maximum pressure rating of the actuator. The double<br />

acting relay is adjusted at the factory <strong>and</strong> set to 70% of supply pressure. If adjustment is<br />

required consult the factory.<br />