Table 81. Doors form fields (continued)<br />

Field<br />

Door Sensor<br />

Description<br />

Click Door Sensor to display the Input list box. Select the desired input for this door sensor. A door sensor<br />

is associated with a digital input (DI) point connected to a door sensor.<br />

Note:<br />

Select a door sensor input that is wired to the same micro as the associated door strike output.<br />

The system displays an operator message if you select an input point on the wrong micro. Do not<br />

attach an input group to the input unless the input is a supervised input.<br />

Exit Button<br />

Click Exit to display the Inputs list box. Select the desired input for this exit button. Be sure the Exit Button<br />

Asserts Strike field (in the Door Control box) is set to Enabled.<br />

Note:<br />

Select an exit button input that is wired to the same micro as the associated door strike output.<br />

The system displays an operator message if you select an input point on the wrong micro. Make<br />

sure the exit input is tied to the reader’s valid input group.<br />

Forced<br />

Open In<br />

Group<br />

Click to display the Input Groups list box. Select an input group to activate. The associated alarm is<br />

triggered when a Forced Open condition occurs. (Be sure the Forced Open Monitoring field is set to<br />

Detected.)<br />

Note:<br />

Only Trigger on Input (non-boolean) input groups are displayed in the list boxes.<br />

Held Open<br />

In Group<br />

Click to display the Input Groups list box. Select an input group to activate. The associated alarm is<br />

triggered when a Held Open condition occurs. (Be sure the Held Open Sensing field is set to Detected.)<br />

Note:<br />

Only Trigger on Input (non-boolean) input groups are displayed in the list boxes.<br />

Pre-Alarm In<br />

Group<br />

Click to display the Input Groups list box. Select an input group to activate. The associated alarm is<br />

triggered when a Pre-Alarm condition occurs. (Be sure the Pre-Alarm field is set to Enabled.)<br />

Note:<br />

Only Trigger on Input (non-boolean) input groups are displayed in the list boxes.<br />

Door State<br />

Scheduling<br />

Held Open<br />

Sensing<br />

Forced<br />

Open<br />

Monitoring<br />

Exit Button<br />

Asserts<br />

Strike<br />

Pre-Alarm<br />

Indicate whether the door is normally Locked (pending a valid badge read or other event) or Unlocked.<br />

Select Enabled to allow scheduled changes set for this door to take place. Select Disabled to prevent<br />

scheduled changes set for this door from taking place.<br />

Select Detected to allow an alarm condition to occur on this door when the door remains open (with a valid<br />

badge reader or exit button) for too long, based on the Allowable Open Time (set in the Door Values box).<br />

Select Ignored if the sensing function on this door is not used.<br />

Select Detected to allow an alarm condition on this door to occur immediately when the door is forced<br />

open without a valid badge read or exit device. Select Ignored if the Monitoring function on this door is not<br />

used.<br />

Select Enabled to allow an exit button to unlock this door for the number of seconds in the Unlock Time<br />

field and remain open for the number of seconds in the Allowable Open Time field (both set in the Door<br />

Values box). Be sure to make a selection in the Exit Button field in the Inputs box. Select Disabled if an exit<br />

button is not allowed to unlock this door but will shunt the door DI.<br />

Select Enabled to allow the Pre-alarm Notification feature to activate. See Pre-alarm notification on<br />

page 373 for details on this feature. Select Disabled if the Pre-alarm Notification feature is not used.<br />

Note:<br />

Input groups for the above can be generic, that is, one input group and alarm can be used by all<br />

doors for forced, held, and pre-alarm.<br />

Keypad<br />

Alarm<br />

Response<br />

Select Enabled to allow the Keypad Alarm Response feature to activate. See Controlling alarms using a<br />

keypad code on page 376 for details on this feature. Select Disabled if the Keypad Alarm Response<br />

feature is not used.