Chapter 18<br />

Advanced features<br />

365<br />

Defining readers<br />

Required for:<br />

• Reader/DO Configuration<br />

• Reader/DI/DO Configuration<br />

Use the Reader form to define the reader type as Elevator for each reader used with an elevator in<br />

the <strong>Picture</strong> <strong>Perfect</strong> system. See Defining readers on page 175.<br />

Defining outputs<br />

Use the Output form to define a digital output for each elevator floor button. This output lights and<br />

activates the button for a floor to which access is allowed. For more information, see Defining outputs<br />

on page 152.<br />

Keep the following in mind when defining elevator floor outputs:<br />

• At least one 16-digital-output (16 DO/DOR) board must be configured with an elevator micro.<br />

• The elevator digital-output addresses must be in the 16 to 31 range for each 16 DO/DOR<br />

board used.<br />

• For a maximum configuration (64 floors), four 16 DO/DOR boards must be installed in a<br />

Micro/5.<br />

• The duration time should be the same for all elevator digital outputs.<br />

Note:<br />

In a Reader/DI/DO configuration, make sure the Reader Interval Time does not exceed the Output (DO)<br />

Duration.<br />

• Elevator digital outputs do not require output groups to be associated with them.<br />

Defining inputs<br />

Required for: Reader/DI/DO Configuration<br />

Use the Input form to define a digital input for each elevator floor button. When this input is received<br />

by the micro, it performs a category match and if successful, activates the associated output for a<br />

floor to which access is allowed. For more information, see Defining inputs on page 155.<br />

Keep the following in mind when defining elevator floor inputs:<br />

• Toggle the Elevator Point button to On to make this input an elevator input.<br />

• At least one 20DI board must be configured with an elevator configured to have the Reader/<br />

DI/DO configuration.<br />

• For a maximum configuration (39 floors), an 8RP reader configured to be an elevator reader,<br />

two 20DI boards and two 16DO boards must be installed in a Micro/5.<br />

• Elevator DI’s do not require an input group to be associated with them.<br />

Elevators form<br />

Use the Elevators form to select the type of elevator configuration, define the number of floors,<br />

assign the elevator to a previously defined elevator micro or reader and then tie previously defined