nanodac RECORDER/CONTROLLER: USER GUIDEB2.6.9 EFFECT OF CONTROL ACTION, HYSTERESIS AND DEADBAND (Cont.)HYST.CSPHYST.HHeating and cooling typeboth ‘On/Off’.Setpoint = 300°CControl action = RevOP1OP2HEATINGCOOLINGHEATINGHeating hysteresis = 8 °CCooling hysteresis = 10°CHeating off atSP (300°C)Coolingon atSP+ HYST.C(310°C)Coolingoff at SP(300°C)Heatingon atSP- HYST.H(292°C)Heating offat SP(300°C)Figure B2.6.9a Deadband OFFHYST.CD.BANDSPHYST.HHeating and cooling typeboth ‘On/Off’.Setpoint = 300°CControl action = RevOP1OP2HEATINGCOOLINGHEATINGHeating hysteresis = 8 °CCooling hysteresis = 10°CPower deadbandHeating off atSP (300°C)Coolingon atSP+ HYST.C(310°C)Coolingoff atD.BAND(305°C)Heatingon atSP- HYST.H(292°C)Heating offat SP(300°C)Figure B2.6.9b Deadband ON set at 50% of Cooling.Appendix BPage 324HA030554Issue 7 Nov 12