nanodac RECORDER/CONTROLLER: USER GUIDE4.4.1 Channel MainThis section describes all possible menu items, but it should be noted that some items are context dependent(e.g. Cold Junction settings appear only for Type = ‘Thermocouple’).Channels one to four in the configuration relate to An In 1 (terminals 1I, 1+ and 1-) to An In 4 (terminals 4I,4+ and 4-) respectively - see figure 2.2.Channel.1.MainDescriptorTypePVStatusIP Adjust StateResolutionUnitsTest SignalInput LowInput HighShuntLin TypeRange LowRange HighRange UnitsScale LowScale HighOffsetCJ TypeExt CJ TempFilterSensor Break TypeFault ResponseSensor Break ValMeasured ValueInternal CJ TempChannel 1Thermocouple197.35GoodAdjusted2°CTriangle 5 Hr0102.49Type K0.00100.00°C0.00100.000.000External0.001.0 secBreak HighDrive Low1%0.235.1Figure 4.4.1a Channel main menu (expanded)Note: For the sake of completeness, the figure above shows all possible fields, even though manyare mutually exclusive. For example, ‘Test signal’ appears only when ‘Test’ is selected as Type. Itwould never appear when Type = thermocouple (as shown). Similarly, ‘Shunt’ would appear only forType = mA.Page 80HA030554Issue 7 Nov 12