Setting parameters04/07 AWB8230-1541GBNotes about changing settings in the second parametersethFunctions SET and SP-SET can not be assigned at thesame time for digital inputs 1 to 6.hFunctions FRS (11), EXT (12), RST (18), PTC (19) and PID(23) must be assigned to the same digital inputs 1 to 5(PNU C001 to C005) in the first and second parameter set(SET or SP-SET). The function is otherwise ignored and thevalue 255 (no function) is written to the respectiveparameters PNU C001 to C005.Table 27: Example – overwriting with values from the second parameter setFirst parameter set Second parameter set (SET, SP-SET) Second/first parameter setC001 00 C201 00 C201/C001 00C002 01 C202 01 C202/C002 01C003 08 [SET] a a C203 08 [SET] C203/C003 255 c pC004 03 C204 53 [SP-SET] b a C204/C004 53 [SP-SET] oC005 18 C205 18 C205/C005 18When you enter the value 08 (SET) in PNU C003 a, the secondparameter set (x2xxx) is activated. The values are the same in bothparameter sets. If you now enter the value 53 (SP-SET) underPNU C204 in the second parameter set b, PNU C004 is alsoautomatically set to 53. Because SET and SP-SET cannot be usedTable 28:Functions with second parameter setDescription of the functionat the same time, the content of PNU C003 and C203 isoverwritten with 255 (no function) c. Digital input 3 now has nofunction. With digital input 4 you can now change between thefirst and second parameter set with special functions (SP-SET). Aparameter set changeover is possible only at standstill (STOP).Parameter number (PNU)Default Second parameter set(STOP) 1) SET (STOP) 1) SP-SET (RUN) 2)First acceleration time F002 F202 F202First deceleration time F003 F203 F203Reference value source selection A001 A201 –Start signal source selection A002 A202 –Base frequency A003 A203 –End frequency (fmax) A004 A204 –<s<strong>tr</strong>ong>Frequency</s<strong>tr</strong>ong> reference input – reference value through keypad, PNU A001 must equal 02. A020 A220 A220Boost, manual voltage boost A042 A242 A242Maximum boost relative to the base frequency A043 A243 A243U/f characteristic A044 A244 –U/f characteristic – output voltage A045 A245 –Maximum operating frequency A061 A261 A261Minimum operating frequency A062 A262 A262Acceleration time 2 A092 A292 A292Deceleration time 2 A093 A293 A293Acceleration time, specify signal for changeover from acceleration time 1 to accelerationtime 2A094 A294 A294Acceleration time, frequency for changeover from ramp time 1 to ramp time 2 A095 A295 A295Deceleration time, frequency for changeover from ramp time 1 to ramp time 2 A096 A296 A296Thermal overload, <strong>tr</strong>ipping current b012 b212 –1) (STOP): Parameters or functions can be activated only in motor stop.2) (RUN): Parameters or functions can be activated during operation.102

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!