Appendix04/07 AWB8230-1541GBPermissible motor cable lengths (EMC)<s<strong>tr</strong>ong>Frequency</s<strong>tr</strong>ong>inverterRFI filterGreatest permissible motorcable length forinterference class…C1 C2 C3DF51-322-025 DE5-LZ1-007-V2 10 m 25 m 25 mDF51-322-037DF51-322-055DF51-322-075 DE5-LZ1-012-V2 10 m 25 m 25 mDF51-322-1K1DF51-322-1K5 DE5-LZ1-024-V2 10 m 25 m 25 mDF51-322-2K2DF51-340-037 DE5-LZ3-007-V4 25 m 50 m 50 mDF51-340-075DF51-340-1K5DF51-340-2K2DF51-340-3K0 DE5-LZ3-011-V4 25 m 50 m 50 mDF51-340-4K0DF51-340-5K5 DE5-LZ3-020-V4 25 m 50 m 50 mDF51-340-7K5C1, C2: first environment (public mains network)C3: Second environment, indus<strong>tr</strong>ial networkRFI filters a page 218Mains contactorshThe mains contactors listed here assume the network’srated current (I LN) without line reactor or mains filter. Their selectionis based on the thermal current (AC-1).h Attention!Jog mode must not be used through the mains contactor(rest period f 180 s between switching off and on).hFor single-phase mains connection, the use of parallelinglink DILM12-XP1 is re<s<strong>tr</strong>ong>com</s<strong>tr</strong>ong>mended to ensure even loadingof all contact decks.DILM12-XP1DILMA11 3 5 13A224 614DILM12-XP1Figure 208:Mains contactor at single-phase connection220