04/07 AWB8230-1541GB Mains contactorsDF51- DF51 phase current Mains contactor DF51 starting current (RCConventional thermal current Part no.load current at maximumI input voltage)th = I e AC-1 at 60 %, openI LN [A] I th AC-1 [A] I 0 [A]Connection 1 ~ 230 V (240 V g 10 %)322-025 3.5 20 DILM7 31.9322-037 5.8322-055 6.7322-075 9322-1K1 11.2322-1K5 17.2322-2K2 24 DILM7 + DILM12-XP1 1)1) For single-phase line connection of the DF51-322-2K2, all three contacts must be connected through paralleling link DILM12-SP1.Connection 3 ~ 230 V (240 V g 10 %)320-4K0 22 35 DILM17 31.9320-5K5 30 35 DILM17320-7K5 40 40 DILM25 16322-025 2 20 DILM7 31.9322-037 3.4322-055 3.9322-075 5.2322-1K1 6.5322-1K5 10322-2K2 143 ~ 400 V connection340-037 2 20 DILM7 63.7340-075 3.3340-1K5 5340-2K2 7340-3K0 10340-4K0 11340-5K5 16.5340-7K5 20 35 DILM17 31.9221