Error messages04/07 AWB8230-1541GBFault signal registerThe DF51 frequency inverter possesses a fault register to which thethree most recent fault messages are saved. You can re<strong>tr</strong>ieve theseunder PNU d081 to d083. PNU d081 shows the most recent faultmessage, PNU d082 last but one, etc. When a new fault occurs, itis saved to PNU d081 and all older faults are moved on by onePNU (PNU d081 a d082, PNU d082 a d083, etc.).PRGPRGPRGPRGabPRGhPRGicHzPRGHzPRGdAPRGAPRGePRGPRGfPRGPRGgPRGPRGFigure 162: Data in the fault register at the time of the fault signala Total number of occurred faultsb Code of the current fault signalc <s<strong>tr</strong>ong>Frequency</s<strong>tr</strong>ong> in Hzd Output current in Ae Internal DC link voltage in Vf Total operating time in h in RUN mode up to the fault signalg POWER ON time in h, power supply switched on up to fault signalh Most recent fault signal (no fault indicated in example)i Last but one fault signalhYou can clear the fault register under PNU b084 (00 or02).182