04/07 AWB8230-1541GB Actual value and status signalsParameterizable digital outputsFigure 109:K12 K14 K11I OAM H O OI L L 5 4 3 2 1 P24 CM2 12 11Digital outputs 11 and 12, CM2Configurable digital outputs 11 and 12 are open collector<strong>tr</strong>ansistor outputs (a fig. 110), to which you can connect, forexample, relays (such as ETS4-VS3, Order No. 083094). Theseoutputs can both be used for various functions, for example tosignal when a determined reference frequency is reached or whena fault occurs.CM211, 12Figure 110: Digital output (sink-type)Transistor output: max. 27 V H, 50 mATerminal CM2 is the <s<strong>tr</strong>ong>com</s<strong>tr</strong>ong>mon reference potential for digitaloutputs 11 and 12. CM2 can be connected to 0 V in sink-type logicand to +24 V in source-type logic (a fig. 51, page 48).Table 30: Digital outputs 11 and 12PNU Terminal Adjustable inRUN modeValueC021 11 – a table 31 01C022 12 00For a detailed description of the output functions, see the pageslisted in table 31.–+DSTable 31:Functions of the digital outputsValue Function Description a Page00 RUN RUN: In operation 11101 FA1 FA1: <s<strong>tr</strong>ong>Frequency</s<strong>tr</strong>ong> referencevalue reached02 FA2 FA2: <s<strong>tr</strong>ong>Frequency</s<strong>tr</strong>ong> signal –output frequency exceedsvalue in PNU C042 (duringacceleration ramp) orPNU C043 (duringdeceleration ramp).03 OL OL: Overload warning – motorcurrent exceeds value inPNU C041.04 OD OD, PID con<strong>tr</strong>ol:Reference/actual valuedifference exceeds signallingthreshold set with PNU C044.11111513105 AL AL: Fault – fault/alarm signal 18306 Dc Dc: Warning – reference valueat input O (0 to +10 V) lowerthan value in PNU b082 orcurrent signal at input OIbelow 4 mA. (reference valuesignal interrupted)07 FBV FBV: PID con<strong>tr</strong>ol – actual valuemonitoring (PV) signal onbreach of limit valuesPNU C052/C053. (actualvalue signal interrupted)08 NDc NDc: Fault/warningdependent on PNU C077 –<s<strong>tr</strong>ong>com</s<strong>tr</strong>ong>munication watchdogtimer has expired:<s<strong>tr</strong>ong>com</s<strong>tr</strong>ong>munications are faulty.09 LOG LOG: Shows result of logic linkperformed throughPNU C143. (High, Low)10 ODc ODc: Fault/warning:Communication overload orinterrupted (with optionalDE51-NET-CAN,DE51-NET-DP). (overload)107

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!