04/07 AWB8230-1541GB Monitoring functionsOverload signal (OL)The overload signal (OL) is output when the current value set withPNU C041 is exceeded.I MC041X To configure digital output 11 or 12 or signalling relay K1 as OL,define the current under PNU C041 at which, when exceeded,the OL signal is activated.X Then configure one of the outputs 11 or 12 as OL by enteringthe value 03 under PNU C021 or C022, or under PNU C026 forsignalling relay K1.LOLP24 CM2 11OL+24 VF 50 mAFigure 121: Function chart for OL (overload signal)I M :Motor currentFigure 122:Digital output 11 configured as an OL (overload signal)PNU Designation RUN b031= 10Value Function DSC041C241Outputfunction –warningthreshold foroverload signal(OL)1) <s<strong>tr</strong>ong>Frequency</s<strong>tr</strong>ong> inverter rated current– j 0…2 x I e [A]Default,dependent onfrequencyinverter’s ratedcurrent (I e )The current value entered here determines when the OL signal shouldbe activated.I e1)115