Using the DF5104/07 AWB8230-1541GBChanging the end frequency: PNU A004X Press the PRG key.X Press the Down key until the main menu A--- shows in thedisplay.X Press the PRG key.The display shows A001.X Press the Up key until A004 shows in the display.X Press the PRG key.The PRG LED lights up. The value set under PNU A004 appears inthe display (default value: 50).X With the Up and Down arrow keys change the set values, forexample to 60 Hz.X Press the PRG key until A--- shows in the display.X Press the Up key until d001 shows in the display.X Press the PRG key.The frequency inverter changes to 0.0 Hz. You have now set theend frequency to 60 Hz, i.e. the previous reference value of 0 to50 Hz now corresponds with 0 to 60 Hz. At50 Hz (PNU A003) themaximum output voltage is reached. Between 50 Hz and 60 Hzonly the output frequency, and therefore the motor’s speedchange.UA003A004As this is a limited operating parameter, you must press the ENTERkey to accept it. If you press the PRG key, the new value isdiscarded.The display shows A004.Figure 61:End frequency 60 HzfENTERPRGPRGPRGaPRG3 xPRGb4 x 3 xPRGFigure 62: Change end frequency (example with default setting)a Display value 0.0 Hzb Parameter holding the displayed value a60