5-16 Parameter Functions and DefinitionsDead BandConditions of Use: The control system must be configured for the heatingand cooling control mode.Function: This parameter allows you to configure the output dead band widthin a heating and cooling control system. A negative setting configures anoverlap band.This parameter sets an area in which the control output is 0 centering aroundthe set point in a heating and cooling control system (see Figure 4.25).The decimal point setting follows the currently set sensor. When using ananalog input, the decimal point setting follows the Decimal Point positionconfiguration.Table 5.QConfigurable Range Units Default Value–199.9…+999.9 EU 0.0Manual Reset ValueConditions of Use: The control mode must be standard control with the2-PID control method configured. In addition, the Integral Time parametermust be set to 0.Function: This parameter allows you to configure the manipulated variable toremove offset during stabilization of P or PD control.Table 5.RConfigurable Range Units Default Value0.0…100.0 % 50.0Related Parameters• PID/ON/OFF (Initial Setting function group) (p. 5-22)• Integral Time (Adjustment function group) (p. 5-14)Publication 900-UM003C-EN-E - January 2004