Parameter Functions and Definitions 5-39Related Parameters• Alarm Value 1 (Operation function group) (p. 5-6)• Upper-Limit Alarm Value 1, Lower-Limit Alarm Value 1 (Operationfunction group) (p. 5-7)• Alarm 1 Type (Initial Setting function group) (p. 5-26)• Standby Sequence Reset Method (Advanced Setting function group)(p. 5-31)• Alarm 1 Open in Alarm (p. 5-32), Alarm 1 Hysteresis (p. 5-32)(Advanced Setting function group)Protect Function Group Move TimeFunction: This parameter allows you to configure the control panel keypressing time required move to the Protect function group from the Operationfunction group or the Adjustment function group.Table 5.ASConfigurable Range Units Default Value1…30 Second 3Related ParameterOperation/Adjustment Protection, Initial Setting/CommunicationsProtection, Setting Change Protection (Protect function group) (p. 5-2)Output Input ErrorConditions of Use: The alarm 1 type must be supported (see Table 1.A). Thecontrol must be set to standard control.Function: When this parameter is configured to ON, the Alarm 1 outputturns ON at an input error condition. Note, however, that the alarm 1operation LED display does not light.The Alarm 1 output is the ORed output of Alarm 1 and Input Error.Publication 900-UM003C-EN-E - January 2004