Appendix CCalibrationParameter StructureThe Bulletin 900-TC32 is correctly calibrated before it is shipped from thefactory, and normally need not be calibrated by the user. If, however, it mustbe calibrated by the user, use the parameters for calibrating temperature inputand analog input.Note: Rockwell Automation cannot ensure the results of calibration by theuser. Also, factory calibration data is overwritten with the user’s settings andthe factory. Default calibration settings cannot be returned after usercalibration.• To calibrate the Bulletin 900-TC32, enter the password 1201 at the Moveto Calibration Function Group parameter in the Advanced Settingfunction group. adj is displayed.• However, note that the Move to Calibration Function Group parametermight not be displayed when, for example, the user is calibrating theBulletin 900-TC32 for the first time. If this happens, set theInitial/Communications Protection parameter in the Protect functiongroup to 0 before moving to the Advanced Setting function group.• The calibration mode is quit by turning the power OFF.C-1 Publication 900-UM003C-EN-E - January 2004