C-8 Calibration5. Press the M key to set the Bulletin 900-TC32 to the state on the left.The No. 2 display at this time displays the currently entered count valueentered in Hexadecimal. Set the STV to 54 mV.Figure 3.166. Allow the count value on the No. 2 display to fully stabilize, then pressthe D key to temporarily register the calibration setup.7. Press the M key to set the Bulletin 900-TC32 to the state on the left. SetSTV to –9 mV.Figure 3.178. Allow the count value on the No. 2 display to fully stabilize, then pressthe D key to temporarily register the calibration setup.9. Press the M key. The No. 2 display changes to the state on the left.Note that the data to be temporarily registered is not displayed when it isnot entirely prepared. Press the U key. The No. 2 display changes toyes. Release the key and wait 2 seconds or press the M key. This storesthe temporarily registered calibration data to EEPROM. To cancelstorage of temporarily registered calibration data to memory, press theM key without pressing the U key.Figure 3.1810. The calibration mode is quit by turning the power OFF.Calibrating PlatinumResistance ThermometersThis example describes how to calibrate the Bulletin 900-TC32 when it isconnected to a platinum resistance thermometer.Figure 3.19900-TC321 2 3 4 5 67 8 9A B BInput powersupply6-dialWhen calibrating a platinum resistance thermometer use wires of the samethickness as those used to connect the Bulletin 900-TC32.Publication 900-UM003C-EN-E - January 2004

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!