5-8 Parameter Functions and DefinitionsRelated Parameters• Alarm 1 Type (Initial Setting function group) (p. 5-26)• Standby Sequence Reset Method (p. 5-31), Alarm 1 Open in Alarm(p. 5-32), Alarm 1 Hysteresis (p. 5-33), Alarm Latch (p. 5-38) (AdvancedSetting function group)MV Monitor (OUT1)Conditions of Use: The Manipulated Variable (MV) display must be set toON.Function: This parameter allows you to monitor the manipulated variable onthe control output 1 side during operation. Table 5.K shows output to controlmode assignment.This parameter cannot be set.During standard control, the manipulated variable is monitored, and duringheating and cooling control, the manipulated variable on the control output 1side is monitored.Note: The default is OFF and the manipulated variable is not displayed.Table 5.I OUT1 ControlControl Mode Monitoring Range UnitsStandard 0.0…100.0 %Heating and cooling 0.0…100.0 %Related ParameterManipulated Variable Display (Advanced Setting function group) (p. 5-37)MV Monitor (OUT2)Conditions of Use: The control mode must be heating and cooling control.The manipulated variable display must be set to ON.Function: This parameter is for monitoring the manipulated variable on thecontrol output 2 side during operation.Publication 900-UM003C-EN-E - January 2004