Parameter Functions and Definitions 5-7Table 5.GConfigurable Range Units Default Value–1999…+9999 EU 0The alarm type must be set to something other than upper and lower limitalarm.Related Parameters• Input Type (p. 5-20), Scaling Upper Limit, Scaling Lower Limit, DecimalPoint (p. 5-20)• Alarm 1 Type (p. 5-26) (Initial Setting function group)• Alarm 1 Open in Alarm (p. 5-32), Alarm 1 Hysteresis (p. 5-33), StandbySequence Reset Method (p. 5-31), Alarm 1 Latch (p. 5-38) (AdvancedSetting function group)Upper-Limit Alarm Value 1,Lower-Limit Alarm Value 1Conditions of Use: The control must be set to standard control. Alarm 1 typemust be set to upper and lower limits, upper and lower limit range, or upperandlower-limit with standby sequence.Function: This parameter allows independent configuration of the upper- andlower-limit alarm values when the mode for setting the upper and lower limitsis selected for Alarm 1 Type (Initial Setting function group).This parameter sets the upper and lower limit values of alarm 1.When using a temperature input, the decimal point position is dependent onthe currently selected sensor, and when using an analog input it is dependenton the Decimal Point parameter setting.Table 5.HConfigurable Range Units Default Value–1999…+9999 EU 0Publication 900-UM003C-EN-E - January 2004