Parameter Functions and Definitions 5-17Hysteresis (OUT1),Hysteresis (OUT2)Conditions of Use: The control must be ON/OFF control.Function: This parameter allows you to configure the hysteresis function tohelp ensure a stable operation during ON/OFF control.• In the standard control mode, use the Hysteresis (OUT1) parameter.The Hysteresis (OUT2) parameter cannot be used in standard control.• In the heating and cooling control mode, the Hysteresis parameter canbe set independently for heating and cooling. Use the Hysteresis(OUT1) parameter to set the Control Output 1 side hysteresis, and usethe Hysteresis (OUT2) parameter to set the Control Output 2 sidehysteresis.• The decimal point setting follows the currently set sensor. Duringanalog input, the decimal point setting follows the Decimal Pointposition setting.Table 5.SConfigurable Range Units Default Value0.1…999.9 EU 1.0Related ParameterPID/ON/OFF (Initial Setting function group) (p. 5-22)Initial Setting FunctionGroupThis function group is for setting up the basic specifications of theBulletin 900-TC32. In this function group, you can set the Input Typeparameter for selecting the sensor input to be connected to theBulletin 900-TC32, limit the range of set points, or set the alarm mode.Publication 900-UM003C-EN-E - January 2004