Parameter Functions and Definitions 5-31Table 5.ADParameter Configurable Range Units Default ValueSP Ramp Set Value OFF, 1…9999 EU OFFRelated ParametersInput Type (p. 5-20), Scaling Upper Limit, Scaling Lower Limit, Decimal Point(p. 5-20), ST (p. 5-23) (Initial Setting function group)Standby Sequence Reset MethodConditions of Use: The alarm 1 type must be configured to “with standbysequence”.Function: Recall that with standby sequence configured the alarm output istemporarily disabled until after the first alarm condition occurs (for moredetails, see p. 4-8). This parameter allows you to configure the conditions (A orB) for enabling alarm reset after the standby sequence of the alarm has beencanceled.The alarm output is turned OFF when switching to either the Initial Settingfunction group, Communications Setting function group, Advanced Settingfunction group, or Calibration function group (see Table 5.AE).• Condition A: Control started (including power ON), and set point,alarm value (upper/lower-limit alarm value) or input shift value(upper/lower-limit temperature input shift value) changed• Condition B: Power ONPublication 900-UM003C-EN-E - January 2004