A-4The applicable standards for each of the above input ranges are as follows:• K, J, T, E, N, R, S, B: JIS C1602-1995, IEC 584-1• L: Fe-CuNi, DIN 43710-1985• U: Cu-CuNi, DIN 43710-1985• JPt100: JIS C 1604-1989, JIS C 1606-1989• Pt100: JIS C 1604-1997 IEC 751Note: The default is set value 0.Control Range• Platinum resistance thermometer and thermocouple input:• –20°C of temperature setting lower limit to +20°C of thetemperature setting upper limit, or• –40°F of temperature setting lower limit to +40°F of the temperaturesetting upper limit• Non-contact input: Same as input indication range• Analog input: –5%…+105% of scaling rangePublication 900-UM003C-EN-E - January 2004