Parameter Functions and Definitions 5-21Table 5.T Scaling Upper Limit, Scaling Lower LimitParameter Configurable Range Units Default ValueScaling Upper Limit Scaling lower limit +1…9999 None 100Scaling Lower Limit –1999 to scaling upper limit –1 None 0Table 5.U Decimal Point: Default is 0: 0 Digits Past Decimal PointSet Value Meaning Example0 0 digits past decimal point 12341 1 digit past decimal point 123.4Related ParameterInput Type (Initial Setting function group) (p. 5-20)°C/°F SelectionConditions of Use: The input type must be configured for a temperatureinput.Function: This parameter allows you to configure the temperature input unitsto either of °C or °F.Table 5.VSelectionsc: °Cf: °FDefault UnitscRelated ParameterInput Type (Initial Setting function group) (p. 5-20)Set Point Upper Limit,Set Point Lower LimitFunction: These parameters allow you to configure the maximum allowablerange for an operator to enter the set point value. The SP can be configuredPublication 900-UM003C-EN-E - January 2004