4-10 Parameter Adjustments and Application ConsiderationsTable 4.B ParametersSymbol Parameter: Function Group Descriptionalh1 Alarm 1 Hysteresis:AlarmAdvanced Setting function grouprest Standby Sequence Reset Method: AlarmAdvanced Setting function groupal1n Alarm 1 Open in Alarm:Advanced Setting function groupAlarmConfiguration of ScalingUpper and Lower Limits(Analog Input)Figure 4.16ScalingupperlimitDecimalpointScalinglower limitOverviewWhen an analog input (0…50 mV voltage input) is selected, scaling toengineering units (e.g., lbs) that match the application is possible.Scaling is configured in the Scaling Upper Limit, Scaling Lower Limit, andDecimal Point parameters (Initial Setting function group). These parameterscannot be used when a temperature input type (e.g., RTD) is selected.The Scaling Upper Limit parameter allows you to configure the physicalquantity to be expressed by the upper limit input value, and the Scaling LowerLimit parameter sets the physical quantity to be expressed by the lower-limitvalue. The Decimal Point parameter specifies the number of digits past thedecimal point.Publication 900-UM003C-EN-E - January 2004