4-4 Parameter Adjustments and Application Considerations2. Prepare a thermometer (B) capable of measuring the temperature of thecontrol target (C) as shown in Figure 4.9 so that 1-point shift or 2-pointshift can be carried out.Figure 4.9 Configuration when Compensating a Non-Contact <strong>Temperature</strong> SensorNon-contacttemperaturesensor(C) Control target(B) Thermometer(A) 900-TC32Using the 1-Point Shift Method1. In the temperature control configuration shown in Figure 4.9, bring theset point to near the value at which the temperature of the control targetis to be controlled. Assume that the control target temperature (C) andthe control target temperature (B) match.Figure 4.102. Check the control target temperature (B) and the controller readout (A).Take the value from the following equation as the Input Shift Value, andconfigure the same numerical values to cns. Figure 4.11 shows theeffect of 1-point temperature input shift.Control target temperature (B) – <strong>Controller</strong> readout (A) =Input shift valuePublication 900-UM003C-EN-E - January 2004