Temperature Controller - Staveb AG

SHOW MORE
SHOW LESS
  • No tags were found...

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

4-14 Parameter Adjustments and Application ConsiderationsExample Operation Procedure — Heating and Cooling Control SelectionStandard/heating and cooling = Heating and cooling1. Press the key for at least 3 seconds to move from the Operationfunction group to the Initial Setting function group.2. Select heating and cooling control in the Initial Setting function group.Figure 4.27stnd: Standard controlh-g: Heating and cooling controlInitial setting function groupStandard/heatingand coolingExample Operation Procedure — Configuring the Dead BandDead band = 51. Select Dead Band in the Adjustment function group.Figure 4.28Adjustment function groupDead band2. Press the U key to set the parameter to 5.0 EU. The setting range is–199.9…+999.9 EU.Figure 4.29Example Operation Procedure — Configuring the Cooling CoefficientCooling coefficient = 101. Select Cooling Coefficient in the Adjustment function group. In thisexample, set the parameter to 10.Figure 4.30Adjustment function groupCoolingcoefficientPublication 900-UM003C-EN-E - January 2004