01/02 AWB8230-1413GB Programmable relay outputsK11 to K34Overload signal (OL)The relay output configured as OL is activated when a freelyselectable motor current is exceeded. The OL output is active aslong as the motor current is higher than this threshold.X To configure a programmable relay output as OL, define thecurrent under PNU C041 at which, when exceeded, the OLsignal is activated.X Then, program one of the relay outputs K23-K24 or K33-K34 asOL output by entering the value 03 under PNU C021 or C022 orin PNU C026 for signalling relay contacts K11K12.OLK23 K245...30 V 0. 250 V DFigure 93:Relay output K23-K24 configured as OL (overload signal)rI MPNU C041OLFigure 94: Function chart for OL (overload signal)I M : Motor currentPNU Name Adjustable in RUN mode Value Function WEC040C041Overload alarmsignalOverload alarmthresholdNormal1) <s<strong>tr</strong>ong>Frequency</s<strong>tr</strong>ong> inverter rated currentExtended– j 00 Always 0101 Only at constant speed0 to 2 x I e1) The current value entered here determines when the OLoverload signal should be activated.I e1)97