.01/02 AWB8230-1413GB Parameter protectionParameter protectionUnder PNU b031, you can specify whether you want to use thenormal or extended parameter setting features in RUN mode. Ifyou set the value 10 under PNU b031, further parameters areavailable which can be modified in the RUN mode. Theseadditional parameters are marked “j” in the Extended column.Adjustable in RUN modeNormal Extended– jThe five following methods of parameter protection are available:PNU Name Adjustable in RUN mode Value Function WENormalExtendedb031Softwaredependentparameterprotection– j 00 Parameter protection through SFT input;all functions inhibited01 Parameter protection through SFT input;input through PNU F001 possible0102 Parameter protection without SFT input;all functions inhibited03 Parameter protection without SFT input;input through PNU F001 possible10 Extended parameters adjustable in RUN mode139