01/02 AWB8230-1413GB Programmable relay outputsK11 to K34Motor thermal overload (THM)The <s<strong>tr</strong>ong>DF6</s<strong>tr</strong>ong> frequency inverters simulate a bimetal element to protectthe motor. With its default setting, it exhibits the illus<strong>tr</strong>atedcharacteristic.J[s]If the motor current is greater than the set <strong>tr</strong>ipping current(dependent on the frequency inverter), the <s<strong>tr</strong>ong>DF6</s<strong>tr</strong>ong> frequency inverterissues fault message E05 <s<strong>tr</strong>ong>and</s<strong>tr</strong>ong> switches the output voltage V2 2off. With a relay output configured as THM, the frequency inverteroutputs a signal before issuing the fault message. The THM outputis activated when the motor exceeds the current set underPNU C061 PNU C061 is the <strong>tr</strong>ipping current in %. The magnitudeof the <strong>tr</strong>ipping current depends on the <strong>tr</strong>ipping characteristicdefined under PNU b013 (a section “Elec<strong>tr</strong>onic motorprotection”, page 135).60THM0.5K23 K240 25.5 A116 %33 A150 %44 A200 %15...30 V 0. 250 V DFigure 102: Tripping characteristic using a <s<strong>tr</strong>ong>DF6</s<strong>tr</strong>ong>-<s<strong>tr</strong>ong>340</s<strong>tr</strong>ong>-11K as anexample, with the <strong>tr</strong>ipping current set to 22 At: Tripping timeI: Motor currentFor a detailed description of how to set parameters PNU b012 tob020 for <strong>tr</strong>ipping, see section “Elec<strong>tr</strong>onic motor protection”,page 135.Figure 103: Relay output K23-K24 configured as THM (motor thermaloverload)X Under PNU C061, enter the percentage value of the <strong>tr</strong>ippingcharacteristic at which the THM output is activated.X Program one of the relay outputs K23-K24 or K33-K34 as THMby entering the value 13 in the corresponding PNU (C021 orC022) or in PNU C026 for signalling relay contacts K11-K12.PNU Name Adjustable in RUN mode Value Function WENormalExtendedC061Thermaloverloadwarning– j 0 to 100 % The entered value relates to the <strong>tr</strong>ipping characteristic setunder PNU b012 to b020.When the value set here is exceeded, the digital outputconfigured as THM is activated.80101

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!