Programming the Con<strong>tr</strong>olSignal Terminals01/02 AWB8230-1413GBPID con<strong>tr</strong>ol deviation signal (OD)The relay output configured as OD is activated when a userdefinable PID deviation (of the actual value from the setpointvalue) is exceeded.The OD output remains active as long as thisdifferential is exceeded.X If you configure a programmable relay output as OD, you mustalso, under PNU C044, enter the threshold at which the ODsignal is activated when the value is exceeded.X Then, program one of the relay outputs K23-K24 or K33-K34 asOD by entering the value 04 in the corresponding PNU (C021 orC022) or in PNU C026 for signalling relay contacts K11-K12.ODK23 K245...30 V 0. 250 V DFigure 95:Relay output K23-K24 configured as OD (PID con<strong>tr</strong>oldeviation)abPNU C044PNU C044ODFigure 96: Function chart for OD (PID con<strong>tr</strong>ol deviation)a Setpointb Actual valuePNU Name Adjustable in RUN mode Value Function WENormalExtendedC044PID regulatordeviation– j 0 to 100 % If the deviation between the setpoint <s<strong>tr</strong>ong>and</s<strong>tr</strong>ong> actual valueexceeds the value entered here when PID con<strong>tr</strong>ol is active,the OD signal is activated.3.098