If the voltage exceeds the value set by the parameter Reference DC-Link Limitation680, the deceleration is reduced in such a way that the DC link voltage is regulated tothe set value. If the DC link voltage cannot be regulated to the set reference value bythe reduction of the deceleration, the deceleration is stopped and the output frequencyraised. The output frequency is calculated by addition of the parameter valueMax. <strong>Frequency</strong> Rise 681 to the frequency at the operating point of the controllerintervention.ParameterSettingsNo. Description Min. Max. Fact. sett.680 Reference DC-Link Limitation U dmin +25V U dmax -25V U d681 Max. <strong>Frequency</strong> Rise 0.00 Hz 999.99 Hz 10.00 HzOperation mode mains failure regulation.Voltage controller: Parameter Operation Mode 670 = 2Ud, fUd672671fGradient limitedby 673 or 683Standard rampor 674Mains voltagePower failureResumption of powertWith the mains failure regulation, short-term mains failures can be bridged. A mainsfailure is recognized if the DC link voltage has fallen below the set value of the parameterMains Failure Threshold 671. If a mains failure is recognized, the controllertries to regulate the DC link voltage to the value set with the parameter ReferenceMains Support Value 672. For this, the output frequency is continuously reduced andthe motor with its rotating masses put into generator operation. The reduction of theoutput frequency is done according to the configuration with a maximum of the currentset by the parameter Gen. Ref. Current Limit 683 or the ramp Mains SupportDeceleration 673.The threshold values of the voltage controller are calculated starting with the currentDC link voltage leading from the parameters Mains Failure Threshold 671 and ReferenceMains support Value 672.If the mains voltage is restored before a switch-off is effected by the mains undervoltagedetection system, the drive is accelerated to its reference frequency at the setacceleration or according to the parameter Acceleration on Mains Resumption 674. Ifthe value of parameter Acceleration on Mains Resumption 674 is set to the defaultvalue of 0.00 Hz/s, the drive is accelerated at the values set for the ramp parametersAcceleration (Clockwise) 420 or Acceleration Anticlockwise 422.146 02/06

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!