16.5.2.1 Limit Value SourcesThe limitation of the frequency can be done by setting fixed values and also by linkingto an analog input parameter. The analog value is limited via parameters MinimumReference Percentage 518 and Maximum Reference Percentage 519, but does notconsider the Gradient Percentage Ramp 477 of the reference percentage valuechannel.The assignment is done for the torque controller via parameters <strong>Frequency</strong> UpperLimit Source 769 and <strong>Frequency</strong> Lower Limit Source 770.Operation modeFunction101 - Analog Input MFI1AThe source is the multifunctional input 1 in ananalog Operation Mode 452.110 - Fixed LimitThe selected parameter values are taken intoaccount to limit the speed controller.201 - Inv. Analog Input MFI1A Operation mode 101, inverted210 - Inv. Fixed Limit Operation mode 110, inverted16.5.3 Speed controllerThe control of the torque-forming current components is done in the outer controlloop by the speed controller. Via parameter Operation Mode 720, you can select theoperation mode for the speed controller. The operation mode defines the use of theparameterizable limits. These are referred to the direction of rotation and the directionof the torque and depend on the selected configuration.Operation mode0 - Speed Controller Off1 -2 -Limits forMotor / GeneratorLimits forpos. / neg. TorqueFunctionThe controller is deactivated or the torque-formingcomponent is zero.The limitation of the speed controller assigns the upperlimit to the motor operation of the drive. Independentof the direction of rotation, the same limit isused. The same applies in the case of regenerativeoperation with the lower limit.The assignment of the limit is done by the sign of thevalue to be limited. Independent of the motor or generatoroperating points of the drive, the positive limitationis done by the upper limit. The lower limit isregarded as a negative limitation.Operation mode 2anticlockwiseclockwiseanticlockwiseclockwisegeneratormotorgeneratormotormotorgeneratornmotorgeneratornCurrent limit 728Current limit generator op. 72902/06 155

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!